Notes applicable to CHeSS HR2,
HC2, HR1, HC1 (year 2000)
1
The specifications list only
the principal components of a heating system affecting energy efficiency.
Other components will be required, such as radiators, circulating pumps,
cisterns, and motorised valves. All components must be selected and sized
correctly.
2
Heating systems should be designed and installed
in accordance with relevant safety regulations, manufacturers' instructions,
the Benchmark scheme (Ref 3), Building Regulations
(Refs 5,6,7), and British Standards (Refs
9, 11). More detailed advice on domestic wet central heating systems
is given in the government's Energy Efficiency Best Practice Programme
Good Practice Guides (Refs 1, 2) and reference
14.
3
A regular boiler does not have the
capability to provide domestic hot water directly, though it may do so
indirectly via a separate hot water store.
A combination (combi) boiler does have the capability to provide
domestic hot water directly, and some models contain an internal hot water
store.
A combined primary storage unit (CPSU) is a boiler with a burner
that heats a thermal store directly. Each of these may be either a condensing
or non-condensing boiler :condensing boilersare always more
efficient.
For further definitions of boiler types see appendix D of reference
12
4
SEDBUK is a measure of the seasonal efficiency
of a boiler installed in typical domestic conditions in the UK. The SEDBUK
efficiency of most current and obsolete boilers can be found on the website
www.boilers.org.uk.
Although SEDBUK is expressed as a percentage, an A to G scale of percentage
bands has also been defined in the following table:
5
A hot water cylinder may be regarded as
meeting or exceeding the insulation requirements of the relevant British
Standard if the manufacturer confirms that the standing heat loss is not
greater than 2.3 x (0.02 x 0.051 V 0.666) kWh per 24 hours, where V is
the capacity in litres. This is equivalent to about 1 watt per litre for
the popular 117 litre cylinder.
6
A high performance hot water cylinder may either be vented
or unvented. The manufacturer must confirm that the heat exchanger and
insulation properties exceed the requirements of the relevant British
Standards (Refs 8, 10) as follows:
The standing heat loss must not exceed 2.0 x (0.02 x 0.051 V 0.666)
kWh per 24 hours, where V is the capacity in litres. This is equivalent
to about 0.85 watts per litre for the popular 117 litre cylinder.
The heat exchanger surface area must be at least 40% greater, or
the performance 40% better, than specified in the relevant standard.
For a vented cylinder of nominal capacity 120 litres the time to re-heat
from 15 deg.C to 60 deg.C should not exceed 20 minutes, where the primary
flow rate is 15 litres per minute at a flow temperature of 82 deg.C.
Differently sized vented cylinders should have a re-heat time in proportion
to capacity (eg; not more than 10 minutes for a 60 litre cylinder).
7
A high performance thermal (primary) storage system must have insulation
properties exceeding by at least 15% those given in the WMA Performance Specification
for Thermal Stores (Ref 4), and comply with the Specification
in other respects.
8
Systems with regular boilers must have separately
controlled circuits to the hot water cylinder and radiators, and both
circuits must have pumped circulation. Large properties should be divided
into zones not exceeding 150 m² floor area, so that heating in each zone
can be timed independently.
9
A time switch is an electrical switch operated by a clock to control
either space heating or hot water, or both together but not
independently.
A full programmer allows the time settings for space heating
and hot water to be fully independent.
A room thermostat measures the air temperature within the building
and switches on and off the space heating. A single target temperature
may be set by the user.
A programmable room thermostat is a combined time switch and room
thermostat which allows the user to set different periods with different
target temperatures for space heating, usually in a daily or weekly cycle.
Some models also allow time control of hot water, so can replace a full
programmer.
A cylinder thermostat measures the temperature of the hot water
cylinder and switches on and off the water heating.
A TRV (thermostatic radiator valve) has an air temperature
sensor which is used to control the heat output from the radiator
by adjusting water flow.
For further definitions and explanations of heating controls see Ref
2.
10
Wireless controls should be designed
with a satisfactory level of immunity to blocking by other radio transmissions.
Otherwise they may become unreliable, or cease to work, as nearby radio
frequency bands become increasingly heavily used from year 2002 onwards.
Products bearing the new "Radiomark" symbol have been certified
to meet this requirement concerning quality, fitness for purpose, and
traceability (see website www.radiomark.org).
For products not bearing the Radiomark, the manufacturer should confirm
that the switching range (and preferably alignment range) do not include
any frequencies below 430 MHz, and that in regard to EN 300 220-1 v1.3.1
(July 2000) the receiver classification (clause 4.1.1) is either Class
1 or Class 2, and the device is marked in accordance with clause 4.3.4.
Compliance with the essential requirements under article 3.2 of the EC
Radio & Telecommunications Terminal Equipment Directive 1999/5/EC is not
sufficient, as the directive is designed only to ensure that wireless
products do not cause harmful interference to other transmissions.
11
Boiler interlock is not a physical
device but an arrangement of the system controls (room thermostats, programmable
room thermostats, cylinder thermostats, programmers and time switches)
so as to ensure that the boiler does not fire when there is no demand
for heat. In a system with a combi boiler it can be achieved by fitting
a room thermostat.
In a system with a regular boiler it can be achieved by correct wiring
interconnection of the room thermostat, cylinder thermostat, and motorised
valve(s). It may also be achieved by more advanced controls, such as a
boiler energy manager. TRVs alone are not sufficient for boiler
interlock.
12
An automatic bypass valve controls water flow in
accordance with the water pressure across it, and is used to maintain
a minimum flow rate through the boiler and to limit circulation pressure
when alternative water paths are closed.
A bypass circuit must be installed if the boiler manufacturer requires
one, or specifies that a minimum flow rate has to be maintained while
the boiler is firing. The installed bypass circuit must then include an
automatic bypass valve (not a fixed position valve).