Backflow prevention devices suitable for fluid protection category 2

 
DUK1 - Anti-vacuum valve combined with a single check valve.

Suitable for protection against; backpressure category 2 and back siphonage category 3. A mechanical device comprising an anti vacuum valve with a single check valve located upstream. No known manufacturer of this product to date

EA - Verifiable single checkvalve

Suitable for protection against backpressure category 2, and back siphonage category 2. Installed in the main feed prior to the appliance. A mechanical device that can be tested in situ; usually via test ports upstream and between the mechanical elements of the device. It will allow water to flow upstream to downstream but not in the reverse direction.

EB - Non verifiable single checkvalve

Suitable for protection against; backpressure category 2, and back siphonage category 2. Installed in the main feed prior to the appliance. A mechanical device that will allow water to flow upstream to downstream but not in the reverse direction.

HA - Hose union backflow preventor.

Suitable for protection against; backpressure category 2 and back siphonage category 3. Simple installation of a backflow preventor to an existing hose union or outside tap. Only permitted on existing installations. A mechanical device for fitting to the outlet of a hose union tap and consisting of a single check valve with air inlets that open if the flow of water ceases.

LA - Pressurised air inlet valve.

Suitable for protection against back siphonage category 2, not acceptable as a backflow prevention device. An anti vacuum or vacuum breaker similar to a type DA but suitable for conditions where the water pressure at the outlet of the device under normal conditions is greater than the atmospheric pressure. Application tends to be limited to locations where waste is acceptable e.g. gardens.

LB - Pressurised air inlet valve combined with a check valve downstream

Suitable for protection against; backpressure category 2 and back siphonage category 3. Same as type LA but single check valve is located downstream. Application tends to be limited to locations where waste is acceptable e.g. gardens.